No response arrived within the APDU timeout. On BACnet/IP this usually means broadcast or routing trouble rather than a dead device.
This is a transport failure, so there is nothing for Forge to normalize: the reading never arrives. What Forge does is refuse to let the gap look like good data. The read-time dropout check flags a field that fell to zero and recovered as a communication glitch rather than a real measurement, and the stuck-sensor check fires when a value repeats for 20 consecutive readings — which is what a cached or last-known value looks like after a link drops. Forge does not retry or reconnect for you; that is your client's or your gateway's job.