FoundryNet / Error codes / Modbus Exception 0B
Modbus error code

Exception 0B (0x0B) — Gateway Target Device Failed To Respond

Returned by a gateway, not by the end device: the gateway is alive and understood the request, but the target behind it did not answer. Exception 0A is the sibling — the gateway could not find a path at all.

Start free Modbus → canonical

Diagnosis

When you hit this


Resolution

How to fix it

  1. Confirm you are talking to a gateway
    0A and 0B can only come from a gateway. Their presence tells you the topology has a hop you may not have accounted for.
  2. Check serial settings on both sides
    Baud, parity, data bits, and stop bits must match exactly. A parity mismatch yields intermittent 0B rather than a clean failure.
  3. Verify the unit ID
    The gateway maps unit ID to a serial address. An unmapped ID gives 0A; a mapped but silent device gives 0B.

Normalization

What Forge does about it

This is a transport failure, so there is nothing for Forge to normalize: the reading never arrives. What Forge does is refuse to let the gap look like good data. The read-time dropout check flags a field that fell to zero and recovered as a communication glitch rather than a real measurement, and the stuck-sensor check fires when a value repeats for 20 consecutive readings — which is what a cached or last-known value looks like after a link drops. Forge does not retry or reconnect for you; that is your client's or your gateway's job.


Connect

Normalize Modbus telemetry

One MCP endpoint serves every protocol adapter. 16,908 curated mappings, 366 canonical fields.

# normalize telemetry from Modbus — and 13 other protocols
claude mcp add --transport http forge https://mcp.foundrynet.io/mcp \
  --header 'Authorization: Bearer YOUR_FORGE_KEY'
✓ forge connected — 32 tools available

Related

Keep reading

Other Modbus codes: Exception 01 Exception 02 Exception 03 Exception 04 Exception 06

Equipment that speaks Modbus: Fanuc Haas Universal Robots Chemical process Food & beverage process Pharma process (GMP) Bridgeport Brother Doosan Robotics Epson Robots

Modbus protocol hub

Other protocols: OPC UA MQTT / Sparkplug B FANUC FOCAS EtherNet/IP PROFINET / S7 BACnet/IP J1939 (CAN) MTConnect ROS 2 (DDS) SNMP MAVLink HTTP / REST CSV ingest

All error codes · All OEMs · All protocols

Industrial AI fails at the data layer. The Machine Agent explains why, weekly. Read it →
Get the thesis behind this infrastructure — The Machine Agent, weekly.